Parameters 179
Supervision 3 Bit 2 of 32.01 Supervision status (see page 184). 26
Other [bit] Source selection (see Terms and abbreviations on page 100). -
31.12 Autoreset selection Selects faults that are automatically reset. The parameter is a
16-bit word with each bit corresponding to a fault type.
Whenever a bit is set to 1, the corresponding fault is
automatically reset.
WARNING! Before you activate the function, make
sure that no dangerous situations can occur. The
function restarts the drive automatically and continues
operation after a fault.
The bits of this binary number correspond to the following
faults:
000Ch
(00…1100b)
0000h…FFFFh Automatic reset configuration word. 1 = 1
31.13 Selectable fault Defines the fault that can be automatically reset using
parameter 31.12 Autoreset selection, bit 10.
Faults are listed in chapter Fault tracing (page 351).
0000h
0000h…FFFFh Fault code. 10 = 1
31.14 Number of trials Defines the number of automatic fault resets the drive
performs within the time defined by parameter 31.15 Tota l
trials time.
5
0…5 Number of automatic resets. 10 = 1
31.15 Total trials time Defines the time the automatic reset function will attempt to
reset the drive. During this time, it will perform the number of
automatic resets defined by 31.14 Number of trials.
30.0 s
1.0…600.0 s Time for automatic resets. 10 = 1 s
31.16 Delay time Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter 31.12
Autoreset selection.
5.0 s
0.0…120.0 s Autoreset delay. 10 = 1 s
31.19 Motor phase loss Selects how the drive reacts when a motor phase loss is
detected.
Fault
No action No action taken. 0
Fault The drive trips on fault 3381 Output phase loss.1
No. Name/Value Description Def/FbEq16
Bit Fault
0 Overcurrent
1Overvoltage
2 Undervoltage
3 AI supervision fault
4…9 Reserved
10 Selectable fault (see parameter 31.13 Selectable fault)
11 External fault 1 (from source selected by parameter 31.01 External event 1 source)
12 External fault 2 (from source selected by parameter 31.03 External event 2 source)
13 External fault 3 (from source selected by parameter 31.05 External event 3 source)
14 External fault 4 (from source selected by parameter 31.07 External event 4 source)
15 External fault 5 (from source selected by parameter 31.09 External event 5 source)