208 Parameters
36.14 PVL DC voltage at
peak
Voltage in the intermediate DC circuit of the drive at the
moment the peak value was recorded.
0.00 V
0.00…2000.00 V DC voltage at peak. 10 = 1 V
36.15 PVL speed at peak Motor speed at the moment the peak value was recorded. 0.00 rpm
-30000.00
30000.00 rpm
Motor speed at peak. See par.
46.01
36.16 PVL reset date The date on which the peak value logger was last reset. 01.01.1980
- Last reset date of the peak value logger. -
36.17 PVL reset time The time at which the peak value logger was last reset. 00:00:00
- Last reset time of the peak value logger. -
36.20 AL1 0 to 10% Percentage of samples recorded by amplitude logger 1 that
fall between 0 and 10%. 100% corresponds to the I
max
value
given in the ratings table in chapter Technical data in the
Hardware manual.
0.00%
0.00…100.00% Amplitude logger 1 samples between 0 and 10%. 1 = 1%
36.21 AL1 10 to 20% Percentage of samples recorded by amplitude logger 1 that
fall between 10 and 20%.
0.00%
0.00…100.00% Amplitude logger 1 samples between 10 and 20%. 1 = 1%
36.22 AL1 20 to 30% Percentage of samples recorded by amplitude logger 1 that
fall between 20 and 30%.
0.00%
0.00…100.00% Amplitude logger 1 samples between 20 and 30%. 1 = 1%
36.23 AL1 30 to 40% Percentage of samples recorded by amplitude logger 1 that
fall between 30 and 40%.
0.00%
0.00…100.00% Amplitude logger 1 samples between 30 and 40%. 1 = 1%
36.24 AL1 40 to 50% Percentage of samples recorded by amplitude logger 1 that
fall between 40 and 50%.
0.00%
0.00…100.00% Amplitude logger 1 samples between 40 and 50%. 1 = 1%
36.25 AL1 50 to 60% Percentage of samples recorded by amplitude logger 1 that
fall between 50 and 60%.
0.00%
0.00…100.00% Amplitude logger 1 samples between 50 and 60%. 1 = 1%
36.26 AL1 60 to 70% Percentage of samples recorded by amplitude logger 1 that
fall between 60 and 70%.
0.00%
0.00…100.00% Amplitude logger 1 samples between 60 and 70%. 1 = 1%
36.27 AL1 70 to 80% Percentage of samples recorded by amplitude logger 1 that
fall between 70 and 80%.
0.00%
0.00…100.00% Amplitude logger 1 samples between 70 and 80%. 1 = 1%
36.28 AL1 80 to 90% Percentage of samples recorded by amplitude logger 1 that
fall between 80 and 90%.
0.00%
0.00…100.00% Amplitude logger 1 samples between 80 and 90%. 1 = 1%
36.29 AL1 over 90% Percentage of samples recorded by amplitude logger 1 that
exceed 90%.
0.00%
0.00…100.00% Amplitude logger 1 samples over 90%. 1 = 1%
36.40 AL2 0 to 10% Percentage of samples recorded by amplitude logger 2 that
fall between 0 and 10%.
0.00%
0.00…100.00% Amplitude logger 2 samples between 0 and 10%. 1 = 1%