Parameters 207
DC voltage 01.11 DC voltage (page 103). 7
Output power 01.14 Output power (page 104). 8
Reserved 9
Speed ref ramp in 23.01 Speed ref ramp input (page 162). 10
Speed ref ramp out 23.02 Speed ref ramp output (page 162). 11
Speed ref used 24.01 Used speed reference (page 163). 12
Reserved 13
Freq ref used 28.02 Frequency ref ramp output (page 167). 14
Reserved 15
Process PID out 40.01 Process PID output actual (page 213). 16
Other Source selection (see Terms and abbreviations on page 100). -
36.02 PVL filter time Peak value logger filtering time. See parameter 36.01 PVL
signal source.
2.00 s
0.00…120.00 s Peak value logger filtering time. 100 = 1 s
36.06 AL2 signal source Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals.
The results are displayed by parameters 36.40…36.49. Each
parameter represents an amplitude range, and shows what
portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter 36.07 AL2 signal scaling.
Amplitude logger 2 can be reset using parameter 36.09 Reset
loggers. The logger is also reset whenever the signal
source or scaling is changed. The date and time of the last
reset are stored into parameters 36.50 and 36.51
respectively.
For the selections, see parameter 36.01
PVL signal source.
Motor torque
36.07 AL2 signal scaling Defines the signal value that corresponds to 100% amplitude. 100.00
0.00…32767.00 Signal value corresponding to 100%. 1 = 1
36.09 Reset loggers Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Done
Done Reset completed or not requested (normal operation). 0
All Reset both the peak value logger and amplitude logger 2. 1
PVL Reset the peak value logger. 2
AL2 Reset amplitude logger 2. 3
36.10 PVL peak value Peak value recorded by the peak value logger. 0.00
-32768.00…
32767.00
Peak value. 1 = 1
36.11 PVL peak date The date on which the peak value was recorded. 01.01.1980
- Peak occurrence date. -
36.12 PVL peak time The time at which the peak value was recorded. 00:00:00
- Peak occurrence time. -
36.13 PVL current at peak Motor current at the moment the peak value was recorded. 0.00 A
-32768.00…
32767.00 A
Motor current at peak. 1 = 1 A
No. Name/Value Description Def/FbEq16