Parameters 219
Supervision 1 Bit 0 of 32.01 Supervision status (see page 184). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 184). 22
Supervision 3 Bit 2 of 32.01 Supervision status (see page 184). 23
Other [bit] Source selection (see Terms and abbreviations on page 100). -
40.21 Set 1 internal
setpoint 1
Internal process setpoint 1. See parameter 40.19 Set 1
internal setpoint sel1.
0.00 PID
customer
units; 5.00
bar
-200000.00…
200000.00 PID
customer units
Internal process setpoint 1. 1 = 1 PID
customer unit
40.22 Set 1 internal
setpoint 2
Internal process setpoint 2. See parameter 40.19 Set 1
internal setpoint sel1.
0.00 PID
customer
units
-200000.00…
200000.00PID
customer units
Internal process setpoint 2. 1 = 1 PID
customer unit
40.23 Set 1 internal
setpoint 3
Internal process setpoint 3. See parameter 40.19 Set 1
internal setpoint sel1.
0.00 PID
customer
units
-200000.00…
200000.00 PID
customer units
Internal process setpoint 3. 1 = 1 PID
customer unit
40.24 Set 1 internal
setpoint 0
Internal process setpoint 0. See parameter 40.19 Set 1
internal setpoint sel1.
0.00 PID
customer
units
-200000.00…
200000.00 PID
customer units
Internal process setpoint 0. 1 = 1 PID
customer unit
40.26 Set 1 setpoint min Defines a minimum limit for the process PID controller
setpoint.
0.00
-200000.00…
200000.00 PID
customer units
Minimum limit for process PID controller setpoint. 1 = 1
40.27 Set 1 setpoint max Defines a maximum limit for the process PID controller
setpoint.
5.00 bar
-200000.00…
200000.00 PID
customer units
Maximum limit for process PID controller setpoint. 1 = 1
40.28 Set 1 setpoint
increase time
Defines the minimum time it takes for the setpoint to increase
from 0% to 100%.
0.0 s
0.0…32767.0 s Setpoint increase time. 1 = 1
40.29 Set 1 setpoint
decrease time
Defines the minimum time it takes for the setpoint to decrease
from 100% to 0%.
0.0 s
0.0…32767.0 s Setpoint decrease time. 1 = 1
No. Name/Value Description Def/FbEq16