EasyManua.ls Logo

ABB ACQ580 - Page 222

ABB ACQ580
422 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
218 Parameters
40.19 Set 1 internal
setpoint sel1
Selects together with 40.20 Set 1 internal setpoint sel2 the
internal setpoint out of the presets defined by parameters
40.2140.24.
Note: Parameters 40.16 Set 1 setpoint 1 source and 40.17
Set 1 setpoint 2 source must be set to Internal setpoint.
Selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 191). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 191). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 191). 20
Supervision 1 Bit 0 of 32.01 Supervision status (see page 184). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 184). 22
Supervision 3 Bit 2 of 32.01 Supervision status (see page 184). 23
Other [bit]
Source selection (see Terms and abbreviations on page 100). -
40.20 Set 1 internal
setpoint sel2
Selects together with 40.19 Set 1 internal setpoint sel1 the
internal setpoint used out of the three internal setpoints
defined by parameters 40.2140.23. See table at 40.19 Set
1 internal setpoint sel1.
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 191). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 191). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 191). 20
No. Name/Value Description Def/FbEq16
Source defined
by par. 40.19
Source defined
by par. 40.20
Setpoint preset active
0 0 0 (par. 40.24)
1 0 1 (par. 40.21)
0 1 2 (par. 40.22)
1 1 3 (par. 40.23)

Table of Contents

Other manuals for ABB ACQ580

Related product manuals