224 Parameters
40.47 Set 1 wake-up
deviation
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay (40.48
Set 1 wake-up delay), the drive wakes up.
See also parameter 40.31 Set 1 deviation inversion.
0.00 PID
customer
units
-200000.00…
200000.00 PID
customer units
Wake-up level (as deviation between process setpoint and
feedback).
1 = 1 PID
customer unit
40.48 Set 1 wake-up
delay
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter 40.47 Set 1 wake-up
deviation.
The delay timer starts when the deviation exceeds the wake-
up level (40.47 Set 1 wake-up deviation), and resets if the
deviation falls below the wake-up level.
0.50 s
0.00…60.00 s Wake-up delay. 1 = 1 s
40.49 Set 1 tracking mode Activates (or selects a source that activates) tracking mode.
In tracking mode, the value selected by parameter 40.50 Set
1 tracking ref selection is substituted for the PID controller
output. See also section Tracking (page 59).
1 = Tracking mode enabled
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 191). 18
Timed function 2 Bit 1 of 34.01
Timed functions status (see page 191). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 191). 20
Supervision 1 Bit 0 of 32.01 Supervision status (see page 184). 21
Supervision 2 Bit 1 of 32.01 Supervision status (see page 184). 22
Supervision 3 Bit 2 of 32.01 Supervision status (see page 184). 23
Other [bit] Source selection (see Terms and abbreviations on page 100). -
40.50 Set 1 tracking ref
selection
Selects the value source for tracking mode. See parameter
40.49 Set 1 tracking mode.
Not selected
Not selected None. 0
AI1 scaled 12.12 AI1 scaled value (see page 125). 1
AI2 scaled 12.22 AI2 scaled value (see page 126). 2
FB A ref1 03.05 FB A reference 1 (see page 106). 3
FB A ref2 03.06 FB A reference 2 (see page 106). 4
Other Source selection (see Terms and abbreviations on page 100). -
No. Name/Value Description Def/FbEq16