226 Parameters
Other [bit] Source selection (see Terms and abbreviations on page 100). -
40.60 Set 1 PID activation
source
Selects the source of process PID set 1 activation. On
Off Set 1 PID activation source is Off. 0
On Set 1 PID activation source is On. 1
Follow Ext1/Ext2
selection
Selection follows the value of parameter 19.11 Ext1/Ext2
selection.
By changing to Ext2 control location, Process PID set 1 is
activated.
2
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 3
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 4
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 5
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 6
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 7
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 8
Other [bit] Source selection (see Terms and abbreviations on page 100). -
40.61 Setpoint actual
scaling
Actual setpoint scaling. See parameter 40.14 Set 1 setpoint
scaling.
50.0
-200000.00…
200000.00 PID
customer units
Scaling. 1 = 1 PID
customer unit
40.62 PID internal
setpoint actual
Displays the value of the internal setpoint. See the control
chain diagram on page 413.
This parameter is read-only.
-
-200000.00…
200000.00 PID
customer units
Process PID internal setpoint. 1 = 1 PID
customer unit
No. Name/Value Description Def/FbEq16