228 Parameters
FB A ref1 03.05 FB A reference 1 (see page 106). 15
FB A ref2 03.06 FB A reference 2 (see page 106). 16
Reserved 17…18
EFB ref1 03.09 EFB reference 1 (see page 107). 19
EFB ref2 03.10 EFB reference 2 (see page 107). 20
Reserved 21…23
Setpoint data
storage
40.92 Setpoint data storage (see page 229)24
40.72 Set 1 compensation
input 1
Point x1 on the setpoint compensation curve, see parameter
40.71 Compensated setpoint.
-200000.00…
200000.00 PID
customer units
Setpoint value. 1 = 1 PID
customer unit
40.73 Set 1 compensated
output 1
Point y1 (= the compensated output of parameter 40.72 Set 1
compensation input 1) on the setpoint compensation curve,
see parameter 40.70 Compensated setpoint.
-200000.00…
200000.00 PID
customer units
Compensated setpoint value. 1 = 1 PID
customer unit
40.74 Set 1 compensation
input 2
Point x2 on the setpoint compensation curve, see parameter
40.71 Compensated setpoint.
-200000.00…
200000.00
Setpoint value. 1 = 1
40.75 Set 1 compensated
output 2
Point y2 (= the compensated output of parameter 40.74 Set 1
compensation input 2) on the setpoint compensation curve,
see parameter 40.70 Compensated setpoint.
-200000.00…
200000.00 PID
customer units
Compensated setpoint value. 1 = 1 PID
customer unit
40.76 Set 1 compensation
non-linearity
Describes the non-linearity of the setpoint compensation
curve, see parameter 40.70 Compensated setpoint.
0…100% Percentage. 1 = 1
40.80 Set 1 PID output
min source
Selects the source for set 1 PID output minimum. Set1 output
min
None None. 0
Set1 output min 40.36 Set 1 output min.1
40.81 Set 1 PID output
max source
Selects the source for set 1 PID output minimum. Set1 output
max
None None. 0
Set1 output max 40.37 Set 1 output max 1
40.89 Set 1 setpoint
multiplier
Defines the multiplier with which the result of the function
specified by parameter 40.18 Set 1 setpoint function is
multiplied.
1.00
-200000.00…
200000.00
Multiplier. 1 = 1
40.90 Set 1 feedback
multiplier
Defines the multiplier with which the result of the function
specified by parameter 40.10 Set 1 feedback function is
multiplied.
1.00
No. Name/Value Description Def/FbEq16