234 Parameters
45.12 Energy tariff 1 Defines energy tariff 1 (price of energy per kWh). Depending
on the setting of parameter 45.14 Tariff selection, either this
value or 45.13 Energy tariff 2 is used for reference when
monetary savings are calculated.
If you have not set the currency during the first start-up, you
can specify it in Main menu - Primary settings - Clock,
region display - Units - Currency.
Note: Tariffs are read only at the instant of selection, and are
not applied retroactively.
0.100 units
0.000…
4294966.296 units
Energy tariff 1. -
45.13 Energy tariff 2 Defines energy tariff 2 (price of energy per kWh).
See parameter 45.12 Energy tariff 1.
0.200 units
0.000…
4294966.296 units
Energy tariff 2. -
45.14 Tariff selection Selects (or defines a source that selects) which pre-defined
energy tariff is used.
0 = 45.12 Energy tariff 1
1 = 45.13 Energy tariff 2
Energy tariff
1
Energy tariff 1 0. 0
Energy tariff 2 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Other [bit] Source selection (see Terms and abbreviations on page 100). -
45.18 CO2 conversion
factor
Defines a factor for conversion of saved energy into CO
2
emissions (kg/kWh or tn/MWh).
0.500
tn/MWh
(metric ton)
0.000…65.535
tn/MWh
Factor for conversion of saved energy into CO
2
emissions. 1 = 1 tn/MWh
45.19 Comparison power Actual power that the motor absorbs when connected direct-
on-line and operating the application. The value is used for
reference when energy savings are calculated.
Note: The accuracy of the energy savings calculation is
directly dependent on the accuracy of this value. If nothing is
entered here, then the nominal motor power is used by the
calculation, but that may inflate the energy savings reported
as many motors do not absorb nameplate power.
0.00 kW
0.00…10000000.00
kW
Motor power. 1 = 1 kW
45.21 Energy calculations
reset
Resets the savings counter parameters 45.01…45.10. Done
Done Reset not requested (normal operation), or reset complete. 0
Reset Reset the savings counter parameters. The value reverts
automatically to Done.
1
No. Name/Value Description Def/FbEq16