Parameters 251
58.25 Control profile Defines the communication profile used by the Modbus
protocol.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter 58.06
Communication control (Refresh settings).
See section About the control profiles on page 371.
ABB Drives
ABB Drives ABB Drives control profile (with a 16-bit control word) 0
DCU Profile DCU control profile (with a 16 or 32-bit control word) 5
58.26 EFB ref1 type Selects the type and scaling of reference 1 received through
the embedded fieldbus interface.
The scaled reference is displayed by 03.09 EFB reference 1.
Speed or
frequency
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. Scaling: 1 = 100. 2
Reserved 3
Speed Speed reference. The scaling is defined by parameter 46.01
Speed scaling.
4
Frequency Frequency reference. The scaling is defined by parameter
46.02 Frequency scaling.
5
58.27 EFB ref2 type Selects the type and scaling of reference 2 received through
the embedded fieldbus interface. The scaled reference is
displayed by 03.10 EFB reference 2.
(The panel at the moment shows Torque as the default, which
cannot be used.)
Speed or
frequency
58.28 EFB act1 type Selects the type of actual value 1. Speed or
frequency
Speed or frequency Type and scaling is chosen automatically according to the
currently active operation mode as follows.
0
Transparent No scaling is applied. 1
General Generic reference without a specific unit. Scaling: 1 = 100. 2
Reserved 3
Speed Scaling is defined by parameter 46.01 Speed scaling.4
Frequency Scaling is defined by parameter 46.02 Frequency scaling.5
58.29 EFB act2 type Selects the type of actual value 2.
For the selections, see parameter 58.28 EFB act1 type.
Transparent
No. Name/Value Description Def/FbEq16
Operation mode
(see par. 19.01)
Reference 1 type
Speed control Speed
Frequency control Frequency
Operation mode
(see par. 19.01)
Actual 1 type
Speed control Speed
Frequency control Frequency

Table of Contents

Other manuals for ABB ACQ580

Related product manuals