258 Parameters
0...8 IPC node number.
76.23 Master enable Selects if this pump operate as a master drive of the IPC
system. The master drive must have sensor connection in
order to control the process.
Selected
Not selected The drive can only be a follower on a inverter-to-inverter link.
Selected The drive can be a master on a inverter-to-inverter link.
76.25 Number of motors Total number of motors used in the application, including the
motor connected directly to the drive.
Note: Parameters are dynamically hidden based on selection
of number of motors.
1
1…8 Number of motors. 1 = 1
76.26 Min number of
motors allowed
Minimum number of motors running simultaneously. 1
0…8 Minimum number of motors. 1 = 1
76.27 Max number of
motors allowed
Maximum number of motors running simultaneously. 1
1…8 Maximum number of motors. 1 = 1
No. Name/Value Description Def/FbEq16

Table of Contents

Other manuals for ABB ACQ580

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACQ580 and is the answer not in the manual?

ABB ACQ580 Specifications

General IconGeneral
Protection classIP21, IP55
Ambient temperature range-15°C to +50°C
Communication protocolsModbus RTU
Mounting typeWall mounted
Control methodvector control
Frequency range0 Hz to 500 Hz
Protection featuresOvercurrent, overvoltage, undervoltage, short circuit