Parameters 257
76.11 Pump status 1 Shows the status of pump or fan 1. -
0000h…FFFFh Status of pump 1. 1 = 1
76.12 Pump status 2 See parameter 76.11 Pump status 1.-
76.13 Pump status 3 See parameter 76.11 Pump status 1.-
76.14 Pump status 4 See parameter 76.11 Pump status 1.-
76.15 Pump status 5 See parameter 76.11 Pump status 1.-
76.16 Pump status 6 See parameter 76.11 Pump status 1.-
76.17 Pump status 7 See parameter 76.11 Pump status 1.-
76.18 Pump status 8 See parameter 76.11 Pump status 1.-
76.21 Multipump
configuration
Selects the multipump mode. Off
Off PFC disabled. 0
IPC IPC enabled. See Intelligent pump control (IPC) on page 60.1
PFC PFC enabled. One pump at a time is controlled by the drive.
The remaining pumps are direct-on-line pumps that are
started and stopped by the drive logic
The frequency (group 28 Frequency reference chain) / speed
(group 22 Speed reference selection) reference must be
defined as PID for the PFC functionality to work properly.
2
SPFC SPFC enabled. See section Soft pump control (SPFC) on
page.64
3
Level control -
Emptying
Level control - Emptying is enabled.
See section Level control on page 65.
4
Level control -
Filling
Level control - Filling is enabled.
See section Level control on page 65.
5
76.22 Multipump node
number
Node number of the drive on inverter-to-inverter link.
Note:
• Each drive on the link has a unique node number.
• If the drive is not given a priority class, the node number is
also used in determining the starting order of the pumps.
1
No. Name/Value Description Def/FbEq16
Bit Name Value
0 Ready 0 = False, 1 = True
1 CRC mismatch 0 = False, 1 = True
2 Running 0 = False, 1 = True
3...4 Reserved
5 In PFC control 0 = False, 1 = True
6 In IPC control 0 = False, 1 = True
7 Master enable 0 = False, 1 = True
8 Active master 0 = False, 1 = True
9...10 Reserved
11 Interlocked 0 = False, 1 = True
12 Local mode 0 = False, 1 = True
13 Reserved
14 Drive start active 0 = False, 1 = True
15 Max stationary time elapsed 0 = False, 1 = True