276 Parameters
Fault Generates D50B Pipe fill-timeout fault. 2
82.26 Time-out limit Defines the delay time at which setpoint must be reached
after last change in PID reference ramp output.
60.0
0.0...1800.0 s Time-out limit in seconds. 1 = 1 s
82.30 Outlet minimum
pressure protection
Enables outlet minimum pressure protection function. Disabled
Disabled Outlet minimum pressure protection function is disabled. 0
Warning Outlet minimum pressure protection function generates D50E
Outlet minimum pressure warning when the outlet minimum
pressure is below the level defined with parameter 82.31
Outlet minimum pressure warning level for a time set in 82.45
Pressure check delay.
1
Fault Outlet minimum pressure protection function generates D408
Outlet minimum pressure fault when the outlet minimum
pressure is below the level defined with parameter 82.32
Outlet minimum pressure fault level for a time set in
parameter 82.45 Pressure check delay.
2
Warning/Fault Outlet minimum pressure protection function first generates a
warning when the pressure is below the level defined with
parameter 82.31 Outlet minimum pressure warning level for a
time set in parameter 82.45 Pressure check delay.
If the pressure continues to fall below the level defined with
parameter 82.32 Outlet minimum pressure fault level, outlet
minimum pressure fault is generated.
3
82.31 Outlet minimum
pressure warning
level
Defines the level at which drive should generate the outlet
minimum pressure warning.
0.00
0.00...32767.00 bar Outlet minimum pressure warning level. 1 = 1 bar
82.32 Outlet minimum
pressure fault level
Defines the level at which drive should generate the outlet
minimum pressure fault.
0.00
0.00...32767.00 bar Outlet minimum pressure fault level. 1 = 1 bar
82.35 Outlet maximum
pressure protection
Enables outlet maximum pressure protection function. Disabled
Disabled Outlet maximum pressure protection is disabled. 0
Warning Outlet maximum pressure protection function generates
D50F Outlet maximum pressure warning when the pressure
is above the level defined with parameter 82.37 Outlet
maximum pressure warning level for a time set in parameter
82.45 Pressure check delay.
1
Fault Outlet maximum pressure protection function generates D409
Outlet maximum pressure fault when the pressure is above
the level defined with parameter 82.38 Outlet maximum
pressure fault level for a time set in parameter 82.45 Pressure
check delay.
2
Warning/Fault Outlet maximum pressure protection function first generates
a warning when the pressure is above the level defined with
parameter 82.37 Outlet maximum pressure warning level for
a time set in parameter 82.45 Pressure check delay.
If the pressure raises above the level defined with parameter
82.38 Outlet maximum pressure fault level, outlet maximum
pressure fault is generated.
3
No. Name/Value Description Def/FbEq16