360 Fault tracing
0003 Maximum torque limit too low. Check settings of parameter 99.12
Motor nominal torque, and the torque
limits in group 30 Limits.
Make sure that the maximum torque
limit in force is greater than 100%.
0004 Current measurement
calibration did not finish within
reasonable time
Contact your local ABB
representative.
0005…0008 Internal error. Contact your local ABB
representative.
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
Contact your local ABB
representative.
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
Contact your local ABB
representative.
000B (Asynchronous motors only)
Speed dropped to zero during
ID run.
Contact your local ABB
representative.
000C (Permanent magnet motors
only)
First acceleration did not finish
within reasonable time.
Contact your local ABB
representative.
000D (Permanent magnet motors
only)
Second acceleration did not
finish within reasonable time.
Contact your local ABB
representative.
000E…0010 Internal error. Contact your local ABB
representative.
0011 (Synchronous reluctance
motors only)
Pulse test error.
Contact your local ABB
representative.
0012 Motor too large for advanced
standstill ID run.
Check that the motor and drive sizes
are compatible.
Contact your local ABB
representative.
0013 (Asynchronous motors only)
Motor data error.
Check that the motor nominal value
settings in the drive are the same as
in the motor nameplate.
Contact your local ABB
representative.
FF63 STO diagnostics
failure.
SW internal malfunction. Reboot the control unit (using
parameter 96.08 Control board boot)
or by cycling power.
FF81 FB A force trip A fault trip command has been
received through fieldbus
adapter A.
Check the fault information provided
by the PLC.
FF8E EFB force trip A fault trip command has been
received through the
embedded fieldbus interface.
Check the fault information provided
by the PLC.
Code
(hex)
Fault / Aux. code Cause What to do