Fieldbus control through the embedded fieldbus interface (EFB) 367
20.06 Ext2
commands
Embedded fieldbus Selects fieldbus as the source for the start
and stop commands when EXT2 is selected
as the active control location.
SPEED REFERENCE SELECTION
22.11 Ext1 speed ref1 EFB ref1 Selects a reference received through the
embedded fieldbus interface as speed
reference 1.
22.18 Ext2 speed ref1 EFB ref1 Selects a reference received through the
embedded fieldbus interface as speed
reference 2.
FREQUENCY REFERENCE SELECTION
28.11 Ext1 frequency
ref1
EFB ref1 Selects a reference received through the
embedded fieldbus interface as frequency
reference 1.
28.15 Ext2 frequency
ref1
EFB ref1 Selects a reference received through the
embedded fieldbus interface as frequency
reference 2.
OTHER SELECTIONS
EFB references can be selected as the source at virtually any signal selector parameter by
selecting Other, then either 03.09 EFB reference 1 or 03.10 EFB reference 2.
SYSTEM CONTROL INPUTS
96.07 Parameter save
manually
Save (reverts to
Done)
Saves parameter value changes (including
those made through fieldbus control) to
permanent memory.
Parameter
Setting for
fieldbus control
Function/Information