260 ACS550 User’s Manual
Technical data
Ratings, 380…480 V drives
Abbreviated column headers are described in section Symbols on page 261.
Type code Normal use Heavy-duty use
Frame
size
ACS550-x1-
see below
I
2N
A
P
N
kW
P
N
hp
I
2hd
A
P
hd
kW
P
hd
hp
Three-phase supply voltage, 380…480 V
-03A3-4 3.3 1.1 1.5 2.4 0.75 1R1
-04A1-4 4.1 1.5 23.31.11.5 R1
-05A4-4 5.4 2.2 Note 1 4.1 1.5 Note 1 R1
-06A9-4 6.9 3
35.42.23R1
-08A8-4 8.8 4
56.933R1
-012A-4 11.9 5.5 7.5 8.8 4 5R1
-015A-4 15.4 7.5 10 11.9 5.5 7.5 R2
-023A-4 23 11
15 15.4 7.5 10 R2
-031A-4 31 15
20 23 11 15 R3
-038A-4 38 18.5 25 31 15 20 R3
-044A-4 (Note 3) 44 22 30 38 18.5 25 R4
-045A-4 (Note 3) 45 22 30 38 18.5 25 R3
-059A-4 59 30 40 44 22 30 R4
-072A-4 72 37 50 59 30 40 R4
-077A-4 (Note 4) 77 Note 2 60 65 Note 2 50 R5
-078A-4 (Note 4) 77 Note 2 60 72 Note 2 50 R4
-087A-4 (Note 5) 87 45 Note 1 77 37 Note 1 R4
-096A-4 (Note 5) 96 45 75 77 37 60 R5
-097A-4 97 Note 2 75 77 Note 2 60 R4
-124A-4 (Note 6) 124 55 100 96 45 75 R6
-125A-4 (Note 6) 125 55 100 96 45 75 R5
-157A-4 157 75 125 124 55 100 R6
-180A-4 180 90 150 156 75 125 R6
-195A-4 195 110 Note 1 162 90 Note 1 R6
-246A-4 245 132 200 192 110 150 R6
00467918.xls B
1. Not available in ACS550-U1 series.
2. Not available in ACS550-01 series.
3. The ACS550-01-045A-4 (an R3 frame size) replaces the ACS550-01-044A-4 (discontinued in
2007).
4. The ACS550-U1-078A-4 (an R4 frame size) replaces the ACS550-U1-077A-4 (discontinued in
2007).
5. The ACS550-01-087A-4 (an R4 frame size) replaces the ACS550-01-096A-4 (discontinued in
2007).
6. The ACS550-01-125A-4 (an R5 frame size) replaces the ACS550-01-124-4 (discontinued in 2007).