Parameters 195
20.26 Jogging 1 start
source
If enabled by parameter 20.25 Jogging enable, selects the
source for the activation of jogging function 1. (Jogging
function 1 can also be activated through fieldbus regardless
of parameter 20.25.)
1 = Jogging 1 active.
Notes:
Jogging is supported in vector control mode only.
If both jogging 1 and 2 are activated, the one that was
activated first has priority.
This parameter cannot be changed while the drive is
running.
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
Reserved 8…17
Timed function 1 Bit 0 of 34.01 Timed functions status (see page 255). 18
Timed function 2 Bit 1 of 34.01 Timed functions status (see page 255). 19
Timed function 3 Bit 2 of 34.01 Timed functions status (see page 255). 20
Reserved 21…23
Supervision 1 Bit 0 of 32.01 Supervision status (see page 248). 24
Supervision 2 Bit 1 of 32.01 Supervision status (see page 248). 25
Supervision 3 Bit 2 of 32.01 Supervision status (see page 248). 26
Other [bit] Source selection (see Terms and abbreviations on page 144
). -
20.27 Jogging 2 start
source
If enabled by parameter 20.25 Jogging enable, selects the
source for the activation of jogging function 2. (Jogging
function 2 can also be activated through fieldbus regardless
of parameter 20.25.)
1 = Jogging 2 active.
For the selections, see parameter 20.26 Jogging 1 start
source.
Notes:
Jogging is supported in vector control mode only.
If both jogging 1 and 2 are activated, the one that was
activated first has priority.
This parameter cannot be changed while the drive is
running.
Not selected
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 195 Wednesday, September 21, 2016 9:48 PM