20 Start-up, control with I/O and ID run
2 – Additional settings: Macro
Select Macro: and press (Select) (or ).
To change the macro in use, select the new macro
and press
(Select), or to go back without
changes, press (Back).
Notes:
Changing macro resets all settings except
motor data to the default values of the selected
macro.
When you change the macro, you also change
the use of the I/O signals in the drive. Make
sure the actual I/O wiring and the use of I/O in
the control program match each other. You can
check the current I/O use in the I/O menu under
the Main menu (see page 22).
To get information on a selected macro, press
.The help page shows the use of signals and
I/O connections. For detailed I/O connection
diagrams, see chapter Control macros on page
59.
Scroll the page with and .
To return to the Control macro submenu, press
(Exit).
All macros, except the ABB standard (vector)
macro, use scalar motor control by default. At
the first start you can select to use scalar or
vector motor control. If you later want to change
the selection, Select Menu - Primary settings -
Motor - Control mode and follow the
instructions.
?