Parameters 241
Reserved 3…14
PID 40.01 Process PID output actual (output of the process PID
controller).
15
Maximum torque 2 30.24 Maximum torque 2.16
Other Source selection (see Terms and abbreviations on page 144). -
30.23 Minimum torque 2 Defines the minimum torque limit for the drive (in percent of
nominal motor torque) when
the source selected by 30.18 Torq lim sel is 1, or
30.18 is set to Torque limit set 2
and
30.21 Min torque 2 source is set to Minimum torque 2.
See diagram at 30.18 To rq lim sel.
WARNING! In torque control mode (vector motor
control) only.
-300.0%
-1600.0…0.0% Minimum torque limit 2. See par.
46.03
30.24 Maximum torque 2 Defines the maximum torque limit for the drive (in percent of
nominal motor torque) when
The limit is effective when
the source selected by 30.18 Torq lim sel is 1, or
30.18 is set to Torque limit set 2
and
30.22 Max torque 2 source is set to Maximum torque 2.
See diagram at 30.18 To rq lim sel.
WARNING! In torque control mode (vector motor
control) only.
300.0%
0.0…1600.0% Maximum torque limit 2. See par.
46.03
30.26 Power motoring
limit
Defines the maximum allowed power fed by the inverter to the
motor in percent of nominal motor power.
300.00%
0.00…600.00% Maximum motoring power. 1 = 1%
30.27 Power generating
limit
Defines the maximum allowed power fed by the motor to the
inverter in percent of nominal motor power.
-300.00%
-600.00…0.00% Maximum generating power. 1 = 1%
30.30 Overvoltage control Enables the overvoltage control of the intermediate DC link.
Fast braking of a high inertia load causes the voltage to rise
to the overvoltage control limit. To prevent the DC voltage
from exceeding the limit, the overvoltage controller
automatically decreases the braking torque.
Note:
If the drive is equipped with a brake chopper and
resistor, or a regenerative supply unit, the controller must be
disabled.
Enable
Disable Overvoltage control disabled. 0
Enable Overvoltage control enabled. 1
No. Name/Value Description Def/FbEq16