Parameters 269
Therm(0) PTC sensor or a normally closed thermistor connected relay
to digital input DI6. The motor is overheated when the digital
input is 0.
21
Therm(1) Normally open thermistor relay connected to digital input DI6.
The motor is overheated when the digital input is 1.
22
35.22 Temperature 2 fault
limit
Defines the fault limit for temperature supervision function 2.
When measured temperature 1 exceeds the limit, the drive
trips on fault 4982 External temperature 2.
The unit is selected by parameter 96.16 Unit selection.
Note: With a PTC sensor, changing the value of this
parameter has no effect on fault generation. When PTC is
over the triggering threshold of the CMOD-02 (see the
Hardware manual), the drive trips on the fault and when PTC
has decreased below recovery threshold of the CMOD-02
(see the Hardware manual), the fault is reset.
130 °C or
266 °F
-60…5000 °C or
-76…9032 °F
Fault limit for temperature monitoring function 2. 1 = 1 unit
35.23 Temperature 2
warning limit
Defines the warning limit for temperature supervision
function 2. When measured temperature 1 exceeds the limit,
warning A492 External temperature 2 is generated.
The unit is selected by parameter 96.16 Unit selection.
Note: With a PTC sensor, changing the value of this
parameter has no effect on warning generation. When PTC is
over the triggering threshold of the CMOD-02 (see the
Hardware manual), the drive trips on the fault and when PTC
has decreased below recovery threshold of the CMOD-02
(see the Hardware manual), the fault is reset.
110 °C or
230 °F
-60…5000 °C or
-76…9032 °F
Warning limit for temperature monitoring function 2. 1 = 1 unit
35.24 Temperature 2 AI
source
Specifies the analog input when the setting of 35.11
Temperature 1 source requires measurement through an
analog input.
Not selected
Not selected None. 0
AI1 actual value Analog input AI1 on the control unit. 1
AI2 actual value Analog input AI2 on the control unit. 2
Other Source selection (see Terms and abbreviations on page 144). -
35.31 Safe motor
temperature enable
Activates or deactivates the Safe motor temperature (SMT)
fault indication (4991 Safe motor temperature)
Off
Off Activated. 0
On Deactivated. 1
35.50 Motor ambient
temperature
Defines the ambient temperature of the motor for the motor
thermal protection model. The unit is selected by parameter
96.16 Unit selection.
The motor thermal protection model estimates the motor
temperature on the basis of parameters
35.5035.55. The
motor temperature increases if it operates in the region above
the load curve, and decreases if it operates in the region
below the load curve.
WARNING! The model cannot protect the motor if the
motor does not cool properly because of dust, dirt, etc.
20 °C or
68 °F
-60…100 °C or
-76…21F
Ambient temperature. 1 = 1°
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 269 Wednesday, September 21, 2016 9:48 PM