Parameters 305
50.11 FBA A act2
transparent source
When parameter 50.08 FBA A actual 2 type is set to
Transparent, this parameter selects the source of actual value
2 transmitted to the fieldbus network through fieldbus adapter
A.
Not selected
Not selected No source selected. -
Other Source selection (see Terms and abbreviations on page 144). -
50.12 FBA A debug mode This parameter enables debug mode. Displays raw
(unmodified) data received from and sent to fieldbus adapter
A in parameters 50.1350.18.
Disable
Disable Debug mode disabled. 0
Fast Debug mode enabled. Cyclical data update is as fast as
possible which increases CPU load on the drive.
1
50.13 FBA A control word Displays the raw (unmodified) control word sent by the
master (PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h…
FFFFFFFFh
Control word sent by master to fieldbus adapter A. -
50.14 FBA A reference 1 Displays raw (unmodified) reference REF1 sent by the master
(PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw REF1 sent by master to fieldbus adapter A. -
50.15 FBA A reference 2 Displays raw (unmodified) reference REF2 sent by the master
(PLC) to fieldbus adapter A if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw REF2 sent by master to fieldbus adapter A. -
50.16 FBA A status word Displays the raw (unmodified) status word sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h…
FFFFFFFFh
Status word sent by fieldbus adapter A to master. -
50.17 FBA A actual value
1
Displays raw (unmodified) actual value ACT1 sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw ACT1 sent by fieldbus adapter A to master. -
50.18 FBA A actual value
2
Displays raw (unmodified) actual value ACT2 sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648…
2147483647
Raw ACT2 sent by fieldbus adapter A to master. -