386 Fault tracing
A8B1 Signal supervision 2
(Editable message text)
Programmable warning:
32.16 Supervision 2 action
Warning generated by the
signal supervision function 2.
Check the source of the warning
(parameter 32.17 Supervision 2 signal).
A8B2 Signal supervision 3
(Editable message text)
Programmable warning:
32.26 Supervision 3 action
Warning generated by the
signal supervision function 3.
Check the source of the warning
(parameter 32.27 Supervision 3 signal).
A8B3 Signal supervision 4
(Editable message text)
Programmable warning:
32.36 Supervision 4 action
Warning generated by the
signal supervision function 4.
Check the source of the warning
(parameter 32.37 Supervision 4 signal).
A8B4 Signal supervision 5
(Editable message text)
Programmable warning:
32.46 Supervision 5 action
Warning generated by the
signal supervision function 5.
Check the source of the warning
(parameter 32.47 Supervision 5 signal).
A8B5 Signal supervision 6
(Editable message text)
Programmable warning:
32.56 Supervision 6 action
Warning generated by the
signal supervision function 6.
Check the source of the warning
(parameter 32.57 Supervision 6 signal).
A8C0 ULC invalid speed
table
User load curve: X-axis points
(speed) are not valid.
Check that points fulfill conditions. See
parameter 37.11 ULC speed table point
1.
A8C1 ULC overload warning User load curve: Signal has
been too long over the
overload curve.
See parameter 37.03 ULC overload
actions.
A8C4 ULC underload
warning
User load curve: Signal has
been too long under the
underload curve.
See parameter 37.04 ULC underload
actions.
A8C5 ULC invalid underload
table
User load curve: Underload
curve points are not valid.
Check that points fulfill conditions. See
parameter 37.21 ULC underload point 1.
A8C6 ULC invalid overload
table
User load curve: Overload
curve points are not valid.
Check that points fulfill conditions. See
parameter 37.31 ULC overload point 1.
A8C8 ULC invalid frequency
table
User load curve: X-axis points
(frequency) are not valid.
Check that points fulfill conditions. -
500.0 Hz <
37.16 < 37.17 < 37.18 <
37.19 < 37.20 <
500.0 Hz. See
parameter 37.16 ULC frequency table
point 1.
A981 External warning 1
(Editable message text)
Programmable warning:
31.01 External event 1
source
31.02 External event 1
type
Fault in external device 1. Check the external device.
Check setting of parameter 31.01
External event 1 source.
A982 External warning 2
(Editable message text)
Programmable warning:
31.03 External event 2
source
31.04 External event 2
type
Fault in external device 2. Check the external device.
Check setting of parameter 31.03
External event 2 source.
Code
(hex)
Warning / Aux. code Cause What to do