276 Parameters
Warning The drive generates an A8C4 ULC underload warning if the
signal has been continuously under the underload curve for a
time defined by parameter 37.42 ULC underload timer.
1
Fault The drive generates an 8001 ULC underload fault if the signal
has been continuously under the underload curve for a time
defined by parameter 37.42 ULC underload timer.
2
Warning/Fault The drive generates an A8C4 ULC underload warning if the
signal has been continuously under the underload curve for
half of the time defined by parameter 37.42 ULC underload
timer.
The drive generates an 8001 ULC underload fault if the signal
has been continuously under the underload curve for a time
defined by parameter 37.42 ULC underload timer.
3
37.11 ULC speed table
point 1
Defines the first of the five speed points on the X-axis of the
user load curve.
The values of the parameters must satisfy: -30000.0 rpm <
37.11 ULC speed table point 1 < 37.12 ULC speed table point
2 < 37.13 ULC speed table point 3 < 37.14 ULC speed table
point 4 < 37.15 ULC speed table point 5 <
30000.0 rpm.
Speed points are used if parameter 99.04 Motor control mode
is set to Vector or if 99.04 Motor control mode is set to Scalar
and the reference unit is rpm.
150.0 rpm
-30000.0…30000.0
rpm
Speed. 1 = 1 rpm
37.12 ULC speed table
point 2
Defines the second speed point.
See parameter 37.11 ULC speed table point 1.
750.0 rpm
-30000.0…30000.0
rpm
Speed. 1 = 1 rpm
37.13 ULC speed table
point 3
Defines the third speed point.
See parameter 37.11 ULC speed table point 1.
1290.0 rpm
-30000.0…30000.0
rpm
Speed. 1 = 1 rpm
37.14 ULC speed table
point 4
Defines the fourth speed point.
See parameter 37.11 ULC speed table point 1.
1500.0 rpm
-30000.0…30000.0
rpm
Speed. 1 = 1 rpm
37.15 ULC speed table
point 5
Defines the fifth speed point.
See parameter 37.11 ULC speed table point 1.
1800.0 rpm
-30000.0…30000.0
rpm
Speed. 1 = 1 rpm
37.16 ULC frequency
table point 1
Defines the first of the five frequency points on the X-axis of
the user load curve.
The values of the parameters must satisfy: -500.0 Hz <
37.16
ULC frequency table point 1 < 37.17 ULC frequency table
point 2 < 37.18 ULC frequency table point 3 < 37.19 ULC
frequency table point 4 < 37.20 ULC frequency table point 5 <
500.0 Hz.
Frequency points are used if parameter 99.04 Motor control
mode is set to Scalar and the reference unit is Hz.
5.0 Hz
-500.0…500.0 Hz Frequency. 1 = 1 Hz
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 276 Wednesday, September 21, 2016 9:48 PM