Fault tracing 393
5691 Measurement circuit
ADC
Measurement circuit fault. Contact your local ABB representative.
5692 PU board powerfail Power unit power supply
failure.
Contact your local ABB representative.
5693 Measurement circuit
DFF
Measurement circuit fault. Contact your local ABB representative.
5696 PU state feedback State feedback from output
phases does not match control
signals.
Contact your local ABB representative.
5697 Charging feedback Charging feedback signal
missing.
Check the feedback signal coming from
the charging system
6181 FPGA version
incompatible
Firmware and FPGA versions
are incompatible.
Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
6306 FBA A mapping file Fieldbus adapter A mapping
file read error.
Contact your local ABB representative.
6481 Task overload Internal fault. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
6487 Stack overflow Internal fault. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
64A1 Internal file load File read error. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
64B2 User set fault Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Ensure that a valid user parameter set
exists. Reload if uncertain.
64E1 Kernel overload Operating system error. Reboot the control unit (using parameter
96.08 Control board boot) or by cycling
power. If the problem persists, contact
your local ABB representative
6581 Parameter system Parameter load or save failed. Try forcing a save using parameter 96.07
Parameter save manually. Retry.
65A1 FBA A parameter
conflict
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups 50
Fieldbus adapter (FBA) and 51 FBA A
settings.
6681 EFB comm loss
Programmable fault: 58.14
Communication loss
action
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
Code
(hex)
Fault / Aux. code Cause What to do