Loading...
Control macros 67
Terminal sizes:
R0…R5: 0.2…2.5 mm
2
(terminals +24V, DGND, DCOM, B+, A-)
0.14…1.5 mm
2
(terminals DI, AI, AO, AGND, RO, STO)
R6…R9: 0.14…2.5 mm
2
(all terminals)
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes:
1)
In scalar control (default): See Menu - Primary settings - Start, stop, reference - Constant
frequencies or parameter group 28 Frequency reference chain.
In vector control
: See Menu - Primary settings - Start, stop, reference - Constant speeds
or parameter group 22 Speed reference selection.
2)
In scalar control (default): See Menu - Primary settings - Ramps or parameter group 28
Frequency reference chain.
In vector control
: See Menu - Primary settings - Ramps or parameter group 23 Speed
reference ramp.
3)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
4)
Connected with jumpers at the factory.
5)
Only frames R6R11 have terminals 40 and 41 for external 24 V AC/DC input.
6)
All control boards do not have switches S1, S2 and S3. In that case, select voltage or current
for inputs AI1 and AI2 and output AO1 with parameters 12.15, 12.25 and 13.15, respectively.
Input signals
Analog speed/frequency reference (AI1)
Start motor forward (DI1)
Start motor in reverse (DI2)
Constant speed/frequency selection (DI3, DI4)
Ramp set (1 of 2) selection (DI5)
Run enable (DI6)
Output signals
Analog output AO1: Output frequency
Analog output AO2: Motor current
Relay output 1: Ready run
Relay output 2: Running
Relay output 3: Fault (-1)
DI3 DI4 Operation/Parameter
Scalar control (default) Vector control
0 0 Set frequency through AI1 Set speed through AI1
1028.26 Constant frequency 1 22.26 Constant speed 1
0128.27 Constant frequency 2 22.27 Constant speed 2
1128.28 Constant frequency 3 22.28 Constant speed 3
DI5 Ramp
set
Parameters
Scalar control (default) Vector control
01 28.72 Freq acceleration time 1 23.12 Acceleration time 1
28.73 Freq deceleration time 1 23.13 Deceleration time 1
12 28.74 Freq acceleration time 2 23.14 Acceleration time 2
Freq deceleration time 2 23.15 Deceleration time 2
ACS580 FW.book Page 67 Wednesday, September 21, 2016 9:48 PM

Table of Contents