Program features 87
Two external control locations, EXT1 and EXT2, are available. The user can select
the sources of the start and stop commands separately for each location in the
Primary settings menu (Menu - Primary settings - Start, stop, reference) or by
setting parameters 20.0120.10. The operating mode can be selected separately for
each location, which enables quick switching between different operating modes, for
example speed and torque control. Selection between EXT1 and EXT2 is done via
any binary source such as a digital input or fieldbus control word (Menu - Primary
settings - Start, stop, reference - Secondary control location or parameter 19.11
Ext1/Ext2 selection). The source of reference is selectable for each operating mode
separately.
Communication fail functionality
The communication fail functionality ensures continuous process without
interruptions. If there is a communication loss, the drive automatically changes the
control location from EXT1 to EXT2. This enables process to be controlled, for
example, with the drive PID controller. When the original control location recovers,
the drive automatically switches control back to the communication network (EXT1).
Block diagram: EXT1/EXT2 selection for speed control
Default =
EXT1
Input 1
Ext1 speed ref1
22.11
Ext1/Ext2 selection
Input 2
Input 3
Input 1
Input 2
Input 3
Ext1 speed ref2
22.12
Function
22.13
Ext1 speed ref1
or a math.
function of Ext1
speed ref1 and
Ext1 speed ref2
Input 1
Ext2 speed ref1
22.18
Input 2
Input 3
Input 1
Input 2
Input 3
Ext2 speed ref2
22.19
Function
22.20
Ext2 speed ref1
or a math.
function of Ext2
speed ref1 and
Ext2 speed ref2
Select
19.11
EXT1
EXT2