Start-up
116
Default values of parameters with the ACS800-17LC
When the IGBT Supply Control Program is loaded into the ACS800-17LC, the
following parameters receive the default values given in the table below. Do not
change the default values. If they are changed, the drive will not operate properly.
31.03 DELAY TIME Defines the time that the drive will wait after a fault before
attempting an automatic reset. See parameter 31.01.
R0 s
0.0 … 3.0 s Resetting delay 0 … 300
31.04 OVERCURRENT Activates/deactivates the automatic reset for the supply unit
overcurrent fault.
BNO
NO Inactive 0
YES Active 65535
31.05 OVERVOLTAGE Activates/deactivates the automatic reset for the intermediate link
overvoltage fault.
BNO
NO Inactive 0
YES Active 65535
31.06 UNDERVOLTAGE Activates/deactivates the automatic reset for the intermediate link
undervoltage fault.
BNO
NO Inactive 0
YES Active 65535
Parameter Default value
11.01 DC REF SELECT FIELDBUS
11.02 Q REF SELECT PARAM 24.02
70.01 CH0 NODE ADDR 120
70.19 CH0 HW CONNECTION RING
70.20 CH3 HW CONNECTION RING
71.01 CH0 DRIVEBUS MODE NO
98.01 COMMAND SEL MCW
98.02 COMM. MODULE INU COM LIM
201.09 PANEL DRIVE ID 2
202.01 LOCAL LOCK TRUE
No. Name/Value Description T./FbEq Def.