Mechanical installation
66
Miscellaneous
Cable duct in the floor below the cabinet
A cable duct can be constructed below the middle part of the cabinet. The duct width
may not exceed 450 mm. The cabinet weight lies on the 100 mm wide section in
front and 50 mm wide section at the back which the floor must carry.
Viewed from above
Side view
This area can be used for a
cable duct
Prevent the cooling air flow from the cable duct to the
cabinet by bottom plates. To ensure the degree of
protection for the cabinet use the original bottom plates
delivered with the unit. With user-defined cable entries,
take care of the degree of protection, fire protection and
EMC compliance.
Cables
50 mm 100 mm
Front
Front
Minimum widths
for the floor support