Mechanical installation
60
Fastening the cabinet to the floor and wall (non-marine units)
Fasten the cabinet to the floor by using clamps along the edge of the cabinet bottom,
or by bolting the cabinet to the floor through the holes inside.
Alternative 1 – Clamping
Insert the clamps into the twin slots along the front and rear edges of the cabinet
frame body and fasten them to the floor with a bolt. The recommended maximum
distance between the clamps is 800 mm (31.5”).
If there is not enough working space behind the cabinet for mounting, replace the
lifting bars at the top with L-brackets (not included) and fasten the top of the cabinet
to the wall.
Clamp dimensions in millimetres
Cabinet frame
Distances between slots
Cubicle
Width
(mm)
Distance in millimetres and (inches)
300 150 (5.9”)
400 250 (9.85”)
500 350 (13.78”)
600 450 (17.72”)
700 550 (21.65”)
800 650 (25.6”)
Cabinet frame
Fastening the cabinet at the top when floor mounting
from back is not possible (side view)
L-bracket
M16 screw
Cabinet top
Slot detail, front view (dimensions in
millimetres)
Side view
View from above