EasyManua.ls Logo

ABB ACS800-17LC - Alternative power cable types; Motor cable shield

ABB ACS800-17LC
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Planning the electrical installation
72
* manufactured before 1.1.1998
** For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.
*** If the intermediate DC circuit voltage of the drive is increased from the nominal level, check with the motor
manufacturer if additional output filters are needed in the applied drive operation range.
Note 1: The abbreviations used in the table are defined below.
Explosion-safe (EX) motors
Consult the motor manufacturer regarding the construction of the motor insulation and additional
requirements for explosion-safe (EX) motors.
N
O
N
-
A
B
B
Random-
wound and
form-wound
U
N
< 420 V Standard: Û
LL
=
1300 V
- + N or CMF + N + CMF
420 V < U
N
< 500 V Standard: Û
LL
=
1300 V
+ du/dt + du/dt + N + du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced: Û
LL
=
1600 V, 0.2
microsecond rise
time
- + N or CMF + N + CMF
500 V < U
N
< 600 V Reinforced: Û
LL
=
1600 V
+ du/dt + du/dt + N + du/dt + N + CMF
or
+ du/dt + CMF
or
Reinforced: Û
LL
=
1800 V
- + N or CMF + N + CMF
600 V < U
N
< 690 V Reinforced: Û
LL
=
1800 V
+ du/dt + du/dt + N + du/dt + N + CMF
Reinforced: Û
LL
=
2000 V, 0.3
microsecond rise
time ***
- N + CMF N + CMF
Abbreviation Definition
U
N
Nominal voltage of the supply network
Û
LL
Peak line-to-line voltage at motor terminals which the motor insulation must withstand
P
N
Motor nominal power
du/dt du/dt filter at the output of the drive +E205
CMF Common mode filter +E208
N N-end bearing: insulated motor non-drive end bearing
n.a. Motors of this power range are not available as standard units. Consult the motor
manufacturer.
Manufacturer
Motor type Nominal AC line
voltage
Requirement for
Motor insulation
system
ABB du/dt filter, insulated N-end bearing and ABB common mode
filter
P
N
< 100 kW
and
frame size < IEC 315
100 kW <
P
N
< 350 kW
or
frame size >
IEC 315
P
N
> 350 kW
or
frame size >
IEC 400
P
N
< 134 hp
and frame size <
NEMA 500
134 hp < P
N
< 469 hp
or frame size >
NEMA 500
P
N
> 469 hp
or frame size >
NEMA 580

Table of Contents

Related product manuals