The temperature of the coolant must be controlled according to the tables below.
Minimum coolant inlet temperature: Condensation is not allowed. The minimum
coolant temperature to avoid concentration (at an atmospheric pressure of 100 kPa)
is shown below as a function of the relative humidity (
ϕ) and the ambient temperature
(T
air
).
= Not allowed as standard but the coolant temperature must be 5 °C or above. Consult an ABB
representative if operation below coolant temperature 5 °C is required.
Example: At an air temperature of 45 °C and relative humidity of 65% the coolant temperature may not
be below +36.8 °C.
Maximum coolant inlet temperature for ACS800 liquid cooled drive
Drive with the optional cooling unit (ACS800-1007LC):
38 °C when the drive output capacity is not derated
38 °C...45 °C when the drive output capacity is derated by 1% per 1 °C
temperature increase.
Drive without the optional liquid cooling unit (ACS800-1007LC):
42 °C when the drive output capacity is not derated
42 °C...48 °C when the drive output capacity is not derated by 1% per 1 °C
temperature increase.
Maximum temperature rise: 13 °C, depends on the mass flow.
T
air
(°C) Min. T
coolant
(°C)
ϕ = 95% ϕ = 80%
ϕ = 65% ϕ = 50% ϕ = 40%
5
4.3 1.9 -0.9 -4.5 -7.4
10 9.2 6.7
3.7 -0.1 -3.0
15 14.2 11.5 8.4
4.6 1.5
20 19.2 16.5 13.2 9.4 6.0
25 24.1 21.4 17.9 13.8 10.5
30 29.1 26.2 22.7 18.4 15.0
35 34.1 31.1 27.4 23.0 19.4
40 39.0 35.9 32.2 27.6 23.8
45 44.0 40.8 36.8 32.1 28.2
50 49.0 45.6 41.6 36.7 32.8
55 53.9 50.4 46.3 42.2 37.1