Parameters 185
10.03 DI force selection The electrical statuses of the digital inputs can be overridden
for eg. testing purposes. A bit in parameter 10.04 DI force
data is provided for each digital input, and its value is applied
whenever the corresponding bit in this parameter is 1.
0000h
0000h…FFFFh Override selection for digital inputs. 1 = 1
10.04 DI force data Contains the values that the digital inputs are forced to when
selected by 10.03 DI force selection.
Bit 0 is the forced value for DI1; bit 15 is the forced value for
the DIIL input.
0000h
0000h…FFFFh Forced values of digital inputs. 1 = 1
10.05 DI1 ON delay Defines the activation delay for digital input DI1. 0.0 s
t
On
= 10.05 DI1 ON delay
t
Off
= 10.06 DI1 OFF delay
*Electrical status of digital input. Indicated by 10.01 DI status.
**Indicated by 10.02 DI delayed status.
0.0 3000.0 s Activation delay for DI1. 10 = 1 s
10.06 DI1 OFF delay Defines the deactivation delay for digital input DI1. See
parameter 10.05 DI1 ON delay.
0.0 s
0.0 3000.0 s Deactivation delay for DI1. 10 = 1 s
No. Name/Value Description Def/FbEq16
Bit Value
0 1 = Force DI1 to value of bit 0 of parameter 10.04 DI force data.
1 1 = Force DI2 to value of bit 1 of parameter 10.04 DI force data.
2 1 = Force DI3 to value of bit 2 of parameter 10.04 DI force data.
3 1 = Force DI4 to value of bit 3 of parameter 10.04 DI force data.
4 1 = Force DI5 to value of bit 4 of parameter 10.04 DI force data.
5 1 = Force DI6 to value of bit 5 of parameter 10.04 DI force data.
6…14 Reserved
15 1 = Force DIIL to value of bit 15 of parameter 10.04 DI force data.
1
0
1
0
t
On
t
Off
t
On
t
Off
*DI status
**Delayed DI status
Time