322 Parameters
33.55 Value counter 1
warn message
Selects the optional warning message for value counter 1. Value
counter 1
exceeded
Value counter 1
exceeded
A88A Value counter 1. The message text can be edited on
the control panel by choosing Menu – Settings – Edit texts.
4
Maintain motor
bearing
A880 Motor bearing.10
33.60 Value counter 2
actual
Displays the actual present value of value counter 2.
The value of the source selected by parameter 33.63 Value
counter 2 source is read at one-second intervals and added
to the counter. A divisor can be applied to the count (see
33.64 Value counter 2 divider).
When the counter exceeds the limit set by 33.61 Value
counter 2 warn limit, bit 5 of 33.01 Counter status is set to 1.
The warning specified by 33.65 Value counter 2 warn
message is also given if enabled by 33.62 Value counter 2
function.
The counter can be reset from the Drive composer PC tool, or
from the control panel by keeping Reset depressed for over 3
seconds.
-
-2147483008 …
2147483008
Actual present value of value counter 2. -
33.61 Value counter 2
warn limit
Sets the limit for value counter 2.
With a positive limit, bit 5 of 33.01 Counter status is set to 1
(and a warning optionally generated) when the counter is
equal or greater than the limit.
With a negative limit, bit 5 of 33.01 Counter status is set to 1
(and a warning optionally generated) when the counter is
equal or smaller than the limit.
0 = Counter disabled.
0
-2147483008 …
2147483008
Limit for value counter 2. -
33.62 Value counter 2
function
Configures value counter 2. 0000b
0000b…0011b Value counter 2 configuration word. 1 = 1
33.63 Value counter 2
source
Selects the signal to be monitored by value counter 2. Not selected
Not selected None (counter disabled). 0
Motor speed 01.01 Motor speed used (see page 152). 1
No. Name/Value Description Def/
FbEq16
Bit Function
0 Counter mode
0 = Loop: When the limit is reached, the counter is reset. The counter status (bit 5 of
33.01) switches to 1 for one second. The warning (if enabled) stays active for at least 10
seconds.
1 = Saturate: When the limit is reached, the counter status (bit 5 of 33.01) switches to 1,
and remains so until 33.60 is reset. The warning (if enabled) also stays active until 33.60
is reset.
1 Warning enable
0 = Disable: No warning is given when the limit is reached
1 = Enable: A warning (see 33.65) is given when the limit is reached
2…15 Reserved