390 Parameters
58.28 EFB act1 type Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through the embedded
fieldbus interface.
Auto
Auto Type/source and scaling follow the type of reference 1
selected by parameter 58.26 EFB ref1 type. See the
individual settings below for the sources and scalings.
0
Transparent The value selected by parameter 58.31 EFB act1 transparent
source is sent as actual value 1. No scaling is applied (the 16-
bit scaling is 1 = 1 unit).
1
General The value selected by parameter 58.31 EFB act1 transparent
source is sent as actual value 1 with a 16-bit scaling of 100 =
1 unit (ie. integer and two decimals).
2
Torque 01.10 Motor torque is sent as actual value 1. The scaling is
defined by parameter 46.03 Torque scaling.
3
Speed 01.01 Motor speed used is sent as actual value 1. The scaling
is defined by parameter 46.01 Speed scaling.
4
Frequency 01.06 Output frequency is sent as actual value 1. The scaling
is defined by parameter 46.02 Frequency scaling.
5
Position Motor position is sent as actual value 1. See parameter 90.06
Motor position scaled.
6
58.29 EFB act2 type Selects the type/source and scaling of actual value 2
transmitted to the fieldbus network through the embedded
fieldbus interface.
Torque
Auto Type/source and scaling follow the type of reference 2
selected by parameter 58.27 EFB ref2 type. See the
individual settings below for the sources and scalings.
0
Transparent The value selected by parameter 58.32 EFB act2 transparent
source is sent as actual value 2. No scaling is applied (the 16-
bit scaling is 1 = 1 unit).
1
General The value selected by parameter 58.32 EFB act2 transparent
source is sent as actual value 2 with a 16-bit scaling of 100 =
1 unit (ie. integer and two decimals).
2
Torque 01.10 Motor torque
is sent as actual value 2. The scaling is
defined by parameter 46.03 Torque scaling.
3
Speed 01.01 Motor speed used is sent as actual value 2. The scaling
is defined by parameter 46.01 Speed scaling.
4
Frequency 01.06 Output frequency is sent as actual value 2. The scaling
is defined by parameter 46.02 Frequency scaling.
5
Position Motor position is sent as actual value 2. See parameter 90.06
Motor position scaled.
6
58.30 EFB status word
transparent source
Selects the source of the status word when 58.25 Control
profile is set to Transparent.
Not selected
Not selected None. 0
Other Source selection (see Terms and abbreviations on page 148). -
58.31 EFB act1
transparent source
Selects the source of actual value 1 when 58.28 EFB act1
type is set to Transparent or General.
Not selected
Not selected None. 0
Other Source selection (see Terms and abbreviations on page 148). -
No. Name/Value Description Def/FbEq16