Parameters 441
Not selected Pump cleaning is not selected. 0
Selected Pump cleaning is selected. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 8
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 9
ESP CW bit 12 Parameter 74.01 ESP control word, bit-12 status controls
enable/disable status of the function.
10
Other Source selection (see Terms and abbreviations on page 148). -
81.02 Pump cleaning
option sel
Defines the control word for the pump cleaning function.
Each bit of this parameter defines either triggering options or
controls certain extensions for the cleaning operation.
0b0010
No. Name/Value Description Def/FbEq16