442 Parameters
81.11 Manual trigger
source
Defines source for the Manual trigger signal necessary to
activate the cleaning operation.
To activate triggering option, set parameter 81.02 Pump
cleaning option sel to bit 1.
Note: The triggering style can be controlled with parameter
81.02 Pump cleaning option sel, bit-14.
There are two possible use cases for cleaning manual trigger.
• When bit-14 is set to 0, cleaning function request is
created only on the rising edge of the source signal. Note,
that the trigger signal must remain ON for the cleaning
request.
• When bit-14 is set to 1, cleaning function request is defined
by the source signal level status. If the trigger signal is ON
all the time, then cleaning operation will be performed at
every start.
ESP CW bit
12
Not selected Manual trigger source is not selected. 0
Selected Manual trigger source is selected. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Reserved
1 Manual trigger Cleaning can be requested by the
manual trigger. See parameter 81.11
Manual trigger source.
2 Time trigger Cleaning can be requested by the time
trigger. See parameter 81.19 Time
trigger.
3...6 Reserved
7 Acceleration boost Enables cleaning acceleration boost.
See parameter 81.35 Acceleration boost
current.
8...9 Reserved
10 Max cleaning supervision Enables supervision for the maximum
allowed number of cleaning.
11 Supervision low Allows low level supervision
automatically interrupt the pump
cleaning procedure.
12 Supervision high Allows high level supervision to skip
current cleaning step cycle.
13 Reserved
14 Manual trig level Sets use-style of the manual trigger to
initiate pump cleaning procedure on
source signal LEVEL.
15 Invert ref sign Invert cleaning procedure speed
reference sign for the both steps.