Parameters 485
96.29 Time sync source
status
Time source status word.
This parameter is read-only.
-
0000h…FFFFh Time source status word 1. 1 = 1
96.31 Drive ID number Specifies an ID number for the drive. The ID can be read by
an external controller through DDCS, for example, for
comparison with an ID contained by the controller’s
application.
0
0…32767 ID number. 1 = 1
96.53 Actual checksum Displays the actual parameter configuration checksum. The
checksum is generated and updated whenever an action is
selected in 96.54 Checksum action.
The parameters included in the calculation have been pre-
selected, but the selection can be edited using the Drive
customizer PC tool.
See also section Parameter checksum calculation (page
126).
0h
00000000h…
FFFFFFFFh
Actual checksum. -
No. Name/Value Description Def/FbEq16
Bit Name Description
0Time tick
received
1 = 1st priority tick received: Tick has been received from 1st priority
source.
1Aux Time
tick received
1 = 2nd priority tick received: Tick has been received from 2nd priority
source.
2Tick interval
is too long
1 = Yes: Tick interval too long (accuracy compromised).
3 DDCS
controller
1 = Tick received: Tick has been received from an external controller.
4Master/
Follower
1 = Tick received: Tick has been received through the master/follower link.
5 Reserved
6 D2D 1 = Tick received: Tick has been received through the drive-to-drive link.
7 FbusA 1 = Tick received: Tick has been received through fieldbus interface A.
8 FbusB 1 = Tick received: Tick has been received through fieldbus interface B.
9 EFB 1 = Tick received: Tick has been received through the embedded fieldbus
interface.
10 Ethernet 1 = Tick received: Tick has been received through the Ethernet port on type
BCU control unit.
11 Panel link 1 = Tick received: Tick has been received from the control panel, or Drive
composer PC tool connected to the control panel.
12 Ethernet tool
link
1 = Tick received: Tick has been received from Drive composer PC tool
through an FENA module.
13 Parameter
setting
1 = Tick received: Tick has been set by parameters 96.2496.26.
14 RTC 1 = RTC time in use: Time and date have been read from the real-time
clock.
15 Drive On-
Time
1 = Drive on-time in use: Time and date are displaying drive on-time.