484 Parameters
Fieldbus A Fieldbus interface A. 3
Fieldbus B Fieldbus interface B. 4
D2D or M/F The master station on a master/follower or drive-to-drive link. 5
Embedded FB Embedded fieldbus interface. 6
Embedded Ethernet Ethernet port on type BCU control unit. 7
Panel link Control panel, or Drive composer PC tool connected to the
control panel.
8
Ethernet tool link Drive composer PC tool through an FENA module. 9
96.23 M/F and D2D clock
synchronization
In the master drive, activates clock synchronization for
master/follower and drive-to-drive communication.
Inactive
Inactive Clock synchronization not active. 0
Active Clock synchronization active. 1
96.24 Full days since 1st
Jan 1980
Number of full days passed since beginning of the year 1980.
This parameter, together with 96.25 Time in minutes within 24
h and 96.26 Time in ms within one minute makes it possible
to set the date and time in the drive via the parameter
interface from a fieldbus or application program. This may be
necessary if the fieldbus protocol does not support time
synchronization.
-
1…59999 Days since beginning of 1980. 1 = 1
96.25 Time in minutes
within 24 h
Number of full minutes passed since midnight. For example,
the value 860 corresponds to 2:20 pm.
See parameter 96.24 Full days since 1st Jan 1980.
0 min
1…1439 Minutes since midnight. 1 = 1
96.26 Time in ms within
one minute
Number of milliseconds passed since last minute.
See parameter 96.24 Full days since 1st Jan 1980.
0 ms
0…59999 Number of milliseconds since last minute. 1 = 1
No. Name/Value Description Def/FbEq16