Parameters 483
96.12 User set I/O mode
in1
When parameter 96.11 User set save/load is set to User set
I/O mode, selects the user parameter set together with
parameter 96.13 User set I/O mode in2 as follows:
Not selected
Not selected 0. 0
Selected 1. 1
DI1 Digital input DI1 (10.02 DI delayed status, bit 0). 2
DI2 Digital input DI2 (10.02 DI delayed status, bit 1). 3
DI3 Digital input DI3 (10.02 DI delayed status, bit 2). 4
DI4 Digital input DI4 (10.02 DI delayed status, bit 3). 5
DI5 Digital input DI5 (10.02 DI delayed status, bit 4). 6
DI6 Digital input DI6 (10.02 DI delayed status, bit 5). 7
DIO1 Digital input/output DIO1 (11.02 DIO delayed status, bit 0). 10
DIO2 Digital input/output DIO2 (11.02 DIO delayed status, bit 1). 11
Other [bit] Source selection (see Terms and abbreviations on page 148). -
96.13 User set I/O mode
in2
See parameter 96.12 User set I/O mode in1. Not selected
96.16 Unit selection Selects the unit of parameters indicating power, temperature
and torque.
0000 0000b
0000 0000b …
0001 0101b
Unit selection word. 1 = 1
96.20 Time sync primary
source
Defines the 1st priority external source for synchronization of
the drive’s time and date.
DDCS
Controller
Internal No external source selected. 0
DDCS Controller External controller. 1
Fieldbus A or B Fieldbus interface A or B. 2
No. Name/Value Description Def/FbEq16
Status of source
defined by par.
96.12
Status of source
defined by par.
96.13
User parameter
set selected
00Set 1
10Set 2
01Set 3
11Set 4
Bit Name Information
0 Power unit 0 = kW
1 = hp
1 Reserved
2 Temperature
unit
0 = C (°C)
1 = F (°F)
3 Reserved
4 Torque unit 0 = Nm (N·m)
1 = lbft (lb·ft)
5…15 Reserved