482 Parameters
96.08 Control board boot Changing the value of this parameter to 1 reboots the control
unit (without requiring a power off/on cycle of the complete
drive module).
The value reverts to 0 automatically.
0
0…1 1 = Reboot the control unit. 1 = 1
96.09 FSO reboot Changing the value of (or the source selected by) this
parameter from 0 to 1 reboots the optional FSO-xx safety
functions module.
Note: The value does not revert to 0 automatically.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 148). -
96.10 User set status Shows the status of the user parameter sets.
This parameter is read-only.
See also section User parameter sets (page 126).
-
n/a No user parameter sets have been saved. 0
Loading A user set is being loaded. 1
Saving A user set is being saved. 2
Faulted Invalid or empty parameter set. 3
User set 1 User set 1 has been loaded. 4
User set 2 User set 2 has been loaded. 5
User set 3 User set 3 has been loaded. 6
User set 4 User set 4 has been loaded. 7
96.11 User set save/load Enables the saving and restoring of up to four custom sets of
parameter settings. See section User parameter sets (page
126).
The set that was in use before powering down the drive is in
use after the next power-up.
Notes:
• Hardware configuration settings such as I/O extension
module, fieldbus and encoder configuration parameters
(groups 14…16, 51…56, 58 and 92…93), parameters
50.01 and 50.31), and forced input/output values (such as
10.03 and 10.04) are not included in user parameter sets.
• Parameter changes made after loading a set are not
automatically stored – they must be saved using this
parameter.
No action
No action Load or save operation complete; normal operation. 0
User set I/O mode Load user parameter set using parameters 96.12 User set I/O
mode in1 and 96.13 User set I/O mode in2.
1
Load set 1 Load user parameter set 1. 2
Load set 2 Load user parameter set 2. 3
Load set 3 Load user parameter set 3. 4
Load set 4 Load user parameter set 4. 5
Save to set 1 Save user parameter set 1. 18
Save to set 2 Save user parameter set 2. 19
Save to set 3 Save user parameter set 3. 20
Save to set 4 Save user parameter set 4. 21
No. Name/Value Description Def/FbEq16