Parameters 481
96.05 Macro active Shows which application macro is currently selected. See
chapter Application macros (page 131) for more information.
To change the macro, use parameter 96.04 Macro select.
Factory
Factory Factory macro (see page 132). 1
Hand/Auto Hand/Auto macro (see page 134). 2
PID-CTRL PID control macro (see page 136). 3
T-CTRL Torque control macro (see page 140). 4
Sequence control Sequential control macro (see page 142). 5
FIELDBUS Fieldbus control macro (see page 145). 6
96.06 Parameter restore Restores the original settings of the control program, ie.
parameter default values.
Note: This parameter cannot be changed while the drive is
running.
Done
Done Restoring is completed. 0
Restore defaults All editable parameter values are restored to default values,
except
• motor data and ID run results
• parameter 31.42 Overcurrent fault limit
• control panel/PC communication settings
• I/O extension module settings
• fieldbus adapter settings
• encoder configuration data
• application macro selection and the parameter defaults
implemented by it
• parameter 95.01 Supply voltage
• parameter 95.09 Switch fuse controller
• differentiated defaults implemented by parameters 95.20
HW options word 1 and 95.21 HW options word 2
• user lock configuration parameters 96.100…96.102.
8
Clear all All editable parameter values are restored to default values,
except
• control panel/PC communication settings
• application macro selection and the parameter defaults
implemented by it
• parameter 95.01 Supply voltage
• parameter 95.09 Switch fuse controller
• differentiated defaults implemented by parameters 95.20
HW options word 1 and 95.21 HW options word 2
• user lock configuration parameters 96.100…96.102.
PC tool communication is interrupted during the restoring.
62
Reset all fieldbus
settings
Fieldbus adapter and embedded fieldbus interface settings
(parameter groups 50…58) are restored to default values.
This will also restore the default settings of the fieldbus
adapter if one is connected.
32
96.07 Parameter save
manually
Saves the valid parameter values to permanent memory. This
parameter should be used to store values sent from a
fieldbus, or when using an external power supply to the
control board as the supply might have a very short hold-up
time when powered off.
Note: A new parameter value is saved automatically when
changed from the PC tool or control panel but not when
altered through a fieldbus adapter connection.
Done
Done Save completed. 0
Save Save in progress. 1
No. Name/Value Description Def/FbEq16