96.02 Pass code Pass codes can be entered into this parameter to activate
further access levels (see parameter 96.03 Access levels
active) or to configure the user lock.
Entering “358” toggles the parameter lock, which prevents the
changing of all other parameters through the control panel or
the Drive composer PC tool.
Entering the user pass code (by default, “10000000”) enables
parameters 96.10096.102, which can be used to define a
new user pass code and to select the actions that are to be
prevented.
Entering an invalid pass code will close the user lock if open,
ie. hide parameters 96.10096.102. After entering the code,
check that the parameters are in fact hidden.If they are not,
enter another (random) pass code.
Note: You must change the default user pass code to
maintain a high level of cybersecurity. Store the code in a safe
place – the protection cannot be disabled even by ABB if the
code is lost.
See also section User lock (page 127).
0
0…99999999 Pass code. -
96.03 Access levels
active
Shows which access levels have been activated by pass
codes entered into parameter 96.02 Pass code.
This parameter is read-only.
0001h
0000h…FFFFh Active access levels. -
96.04 Macro select Selects the application macro. See chapter Application
macros (page 131) for more information.
After a selection is made, the parameter reverts automatically
to Done.
Done
Done Macro selection complete; normal operation. 0
Factory Factory macro (see page 132). 1
Hand/Auto Hand/Auto macro (see page 134). 2
PID-CTRL PID control macro (see page 136). 3
T-CTRL Torque control macro (see page 140). 4
Sequence control Sequential control macro (see page 142). 5
FIELDBUS Reserved. 6
No. Name/Value Description Def/FbEq16
Bit Name
0 End user
1 Service
2 Advanced programmer
3…10 Reserved
11 OEM access level 1
12 OEM access level 2
13 OEM access level 3
14 Parameter lock
15 Reserved

Table of Contents