Parameters 487
96.61 User data logger
status word
Provides status information on the user data logger (see page
567).
0000b
0000b1111b User data logger status word. 1 = 1
96.63 User data logger
trigger
Triggers, or selects a source that triggers, the user data
logger.
Off
Off 0. 0
On 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 148). -
96.64 User data logger
start
Starts, or selects a source that starts, the user data logger. Off
Off 0. 0
On 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 148). -
96.65 Factory data logger
time level
Selects the sampling interval for the factory data logger (see
page 566).
500us
500us 500 microseconds. 500
2ms 2 milliseconds. 2000
10ms 10 milliseconds. 10000
96.70 Disable adaptive
program
Enables/disables the adaptive program (if present).
See also section Adaptive programming (page 63).
No
No Adaptive program enabled. 0
Yes Adaptive program disabled. 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Running 1 = The user data logger is running. The bit is cleared after the post-trigger
time has passed.
1 Triggered 1 = The user data logger has been triggered. The bit is cleared when the
logger is restarted.
2 Data
available
1 = The user data logger contains data that can be read. Note that the bit is
not cleared because the data is saved to the memory unit.
3 Configured 1 = The user data logger has been configured. Note that the bit is not
cleared because the configuration data is saved to the memory unit.
4…15 Reserved