Communication objects
Application "Internal RTC"
Product manual 2CKA001473B5023
184
Object 14 [receive] Input 3 bytes
[232.600]
Colour RGB
K - S U A
Object 15 [send] Output 3 bytes
[232.600]
Colour RGB
K - - U -
Object 15 [receive] Input 3 bytes
[232.600]
Colour RGB
K - S U A
Activate scene x Input 1 bit
[1.010]
Start
K - S - A
Dimming scene x Input 4 bit
[3.007]
Dimming
control
K - S - A
Control On/Off (slave) Input 1 bit
[1.001]
Switching
K - S U A
External actual temperature Input 2 bytes
[9.001]
Temperature
(°C)
K - S U A
Fault, actual temperature
(slave)
Input/
Output
1 bit
[1.001]
Switching
K - S - A
Operating mode
(slave)
Output 1 byte
[20.102]
HVAC mode
K - S U A
Override operating mode
(Master/Slave)
Input/
Output
1 byte
[20.102]
HVAC mode
K - S U A
Proximity function Output 1 bit
[1.001]
Switching
K - - U -
Deactivate proximity function Input 1 bit
[1.002]
Boolean
K S A
Window contact
(master/slave)
Input/
Output
1 bit
[1.001]
Window/door
K - S U A
Presence detector
(master/slave)
Input/
Output
1 bit
[1.001]
Occupancy
K - S U A
Window contact Input 1 bit
[1.001]
Switching
K - S - A
Presence detectors Input 1 bit
[1.001]
Switching
K - S - A
Condensation / fill level
alarm (Master/Slave)
Input/
Output
1 bit
[1.001]
Alarm
K - S U A
Units switchover (slave)
Input/
Output
1 bit
[1.001]
Switching
K - S U A
On/off request (slave) Output 1 bit
[1.001]
Switching
K - - U -
Setpoint display (slave)
Input/
Output
2 bytes
[9.001]
Temperature
(°C)
K - S U A
Request setpoint (slave) Output 2 bytes
[9.001]
Temperature
(°C)
K - - U -
Confirm setpoint (slave)
Input/
Output
2 bytes
[9.001]
Temperature
(°C)
K - S U A
Heating/cooling request
(slave)
Output 1 bit
[5.010]
Heating/Cooli
ng
K - - U -
Heating/cooling request Input 1 bit
[1.100]
Heating/Cooli
ng
K - S - A