Communication objects
Application "Internal RTC"
Product manual 2CKA001473B5023
185
Fan coil manual confirmation
(Master)
Output 1 bit
[1.001]
Switching
K L - U -
Fan coil manual confirmation
(Slave)
Input/
Output
1 bit
[1.001]
Switching
K - S U A
Request fan speed level
manually (slave)
Output 1 bit
[5.010]
Switching
K - - U -
Request fan speed level
manually (master)
Input 1 bit
[1.001]
Switching
K - S - A
Request fan speed level
(slave)
Output 1 byte
[6.010]
Counting
pulses
(-128 - 127)
K - - U -
Request fan speed level
(master)
Input 1 byte
[5.001]
Percent
(0 - 100%)
K - S - A
Confirm fan speed level
(slave)
Input/
Output
1 byte
[6.010]
Counting
pulses
(-128 - 127)
K - S U A
Confirm fan speed level
(master)
Output 1 byte
[5.001]
Percent
(0 - 100%)
K L - U -
Controller status RHCC Output 2 bytes [22,101] K - - U -
Commissioned Output 1 bit
[1.001]
Switching
K - - U -
Setpoint for heating comfort Output 2 bytes
[9.001]
Temperature
(°C)
K - S - A
Setpoint for heating standby Input 2 bytes
[9.001]
Temperature
(°C)
K - S - A
Heating setpoint economy Input 2 bytes
[9.001]
Temperature
(°C)
K - S - A
Heating setpoint for building
protection
Input 2 bytes
[9.001]
Temperature
(°C)
K - S - A
Setpoint for cooling comfort Input 2 bytes
[9.001]
Temperature
(°C)
K - S - A
Setpoint for cooling standby Input 2 bytes
[9.001]
Temperature
(°C)
K - S - A
Cooling setpoint economy Input 2 bytes
[9.001]
Temperature
(°C)
K - S - A
Cooling setpoint for building
protection
Input 2 bytes
[9.001]
Temperature
(°C)
K - S - A
Setpoint error Output 1 bit
[9.001]
Temperature
(°C)
K - - U -
Limit temperature basic
heating stage
Input 2 bytes
[9.001]
Temperature
(°C)
K - S - A

Table of Contents

Related product manuals