other station configuration tool) contains these GOOSE data sets as input data. The
input data must be connected to a GOOSE receive function block
(GOOSEBINRCV) in SMT.
If the quality and time of the value is needed in the receiver IED, the quality and
time must be included in the GOOSE data set. The receiver side will connect this
automatically and if the quality and time is not in the data set, a warning message
will occur in PCM.
8.1.4 Station configuration description file types
SEMOD58549-93 v6
The IEC 61850 standard defines SCL-file types in the sequence of engineering.
These files have a different definition, which is explained in IEC 61850–6. Three
of these file types are used in the engineering process for an IED.
SCL files Description
ICD = IED Capability Description
The IED name in an
exported .icd file is always
named TEMPLATE.
Capability description of the IED in logical
nodes and their data. No information about
communication configuration, for example,
is included.
An IED is already extended by default data
sets. They are predefined by ABB.
Changes or additional data sets, for
example, have to be done with the IET600
station configuration tool.
SCD = Station Configuration Description Complete configuration description of all IEDs in
a station and the full engineering of process
signals and communication structure is included.
This includes all needed data sets and all control
blocks.
CID = Configured IED Description
The CID file contains the information needed to
configure just one specific IED.
The uploading of IEC 61850 communication configuration is not
supported when reading a configuration from an online IED.
8.2 IEC 61850 engineering procedure
8.2.1 IEC 61850 protocol references and pre-conditions
SEMOD58549-4 v4
To engineer the IEC 61850 protocol interface for the IED, the following additional
manuals or knowledge of their contents is required.
Section 8 1MRK 511 398-UEN C
IEC 61850 communication engineering
110 670 series 2.2 IEC
Engineering manual

Table of Contents