The same as LatchedAck-F-S but the LED starts with steady state and
flashes after acknowledgment.
LatchedColl-S
The LED illuminates in all cases in steady mode only
The LED latches a signal change from OFF-ON until it is acknowledged
by the operator.
The LED stays in steady mode when it is reset and the signal is still in
ON state.
The LED is OFF only after the signal has changed to OFF state AND it
is reset by the operator via 'Clear' operation.
LatchedReset-S
This mode is used for all LEDs that are used to indicate a disturbance.
The LEDs will stay in the last state after the disturbance run time until
they are reset after a defined time.
The timers are set in the Parameter Setting tool in the function block
LEDGEN.
IEC09000657-1-en.vsd
IEC09000657 V1 EN-US
Figure 50: LHMI: LED operation mode
7.1.2 LED operation modes
GUID-40B89A33-3C2D-488C-8932-F862E0C9F477 v4
The SequenceType parameter enables each LED to operate in one out of six
different modes.
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
Section 7 1MRK 511 398-UEN C
Local HMI engineering
88 670 series 2.2 IEC