IEC09000631 V3 EN-US
Figure 87: IEC 61850: Import SCD file
4.1. Select Ignore Substation Section to ignore the sub-station section in the
SCD file during import.
4.2. Select Don't import IEDs ... to disable the import of unknown IED types
(for example third-party IEDs).
4.3. Select Replace unknown ... to replace unknown IED types with IED type
“Generic IEC 61850 IED”. Use this option if you need to import third-
party IEDs into PCM600.
4.4. Select Ignore PCM Object Type if the IED type is modified outside
PCM600.
4.5. Click Import.
5. Configure how to receive data from sending IEDs:
5.1. In SMT, configure connections between signals the server is sending and
the GOOSE receive function blocks.
If a client is defined for GOOSE receive, at least one cross in
SMT is required to write the configuration to the IED.
It is important to set Operation to On for all configured
GOOSE receiving function blocks.
8.6.2 Importing ICD or CID files
GUID-D8A6D372-7E16-4004-AAF6-F6E3BAC64E30 v3
Procedure to import an ICD or CID file:
1MRK 511 398-UEN C Section 8
IEC 61850 communication engineering
670 series 2.2 IEC 129
Engineering manual