IEC16000169 V1 EN-US
Figure 86: ACT: GOOSESenderApp
GOOSE datasets and GOOSE control blocks are created
automatically when the GOOSE configuration is done in ACT.
If the sender IED and receiver IEDs do not belong to same
subnetworks, GOOSE receiving is not possible.
Creation of GOOSE communication for GOOSEVCTRRCV
function via Easy GOOSE Engineering is not supported.
GOOSESenderApp MainApp cannot be copied or deleted in the
Application Configuration.
8.4.3.5 Easy GOOSE engineering when GOOSE is configured via
IEC 61850 configuration protocol
GUID-0D498334-DB06-4038-9FAB-D9ADE2585D51 v1
After enabling Easy GOOSE Engineering in PCM600 (see section "Enable Easy
GOOSE Engineering in PCM600"), GOOSE can be configured either via the
IEC 61850 configuration tool and the Signal matrix tool or via Easy GOOSE.
When GOOSE is configured via the IEC 61850 configuration tool and Signal
matrix tool, the GOOSE configuration is also added to the application
configuration in the sender IED and the receiver IED as shown in Figure
81, 82,
84, and 85.
When Easy GOOSE engineering is enabled in PCM600, GOOSE
can be still be configured via IEC 61850 configuration tool and
Signal Matrix Tool as well.
1MRK 511 398-UEN C Section 8
IEC 61850 communication engineering
670 series 2.2 IEC 125
Engineering manual