1. Select an IED in the plant structure.
2. Right-click on the IED and select Import ...
3. Select the file to be imported.
4. An SCL Import Options window opens to enable you to configure import
handling (see
Figure 88):
4.1. Select Ignore Substation Section to ignore the sub-station section in the
chosen file during import.
4.2. Select Don't import IEDs ... to disable the import of unknown IED types
(for example third-party IEDs).
4.3. Select Replace unknown ... to replace unknown IED types with IED type
“Generic IEC 61850 IED”. Use this option if you need to import third-
party IEDs into PCM600.
4.4. Select Ignore PCM Object Type if the IED type is modified outside
PCM600.
4.5. Click Import.
IEC09000631 V3 EN-US
Figure 88: IEC 61850: SCL Import option
8.7 Writing IEC 61850 communication configuration to
an IED
GUID-EE2F7AE2-2EA6-4F16-94F1-E9472CF6BB50 v5
When a changed IEC 61850 communication configuration is written to an IED, the
user can select to update the communication configuration by clicking the batch
write button in the toolbar.
If batch writing is not used the user is asked to update the communication
configuration:
Section 8 1MRK 511 398-UEN C
IEC 61850 communication engineering
130 670 series 2.2 IEC
Engineering manual